4. Operation
4.3.6.2.1 System Setup
Click the System Setup icon. Select the conguration to be changed/saved. Click the Back icon to return to the
previous window, or click the Home Page icon to jump to the main page.
AdvancedSystemSetupCongurations
Working Mode: Select the work mode of UPS, work mode: Single Mode, Parallel Mode, ECO Mode, ECO+Parallel
Machine Mode. Default value: ECO Mode.
Auto Turn-On: Select the UPS start logic. Enable (default is Enable): The UPS starts inverter output automatically.
Disable: No output. Note: If you want the UPS to auto restart after the batteries reach a low voltage cut-o and the UPS turns o, Auto
Turn-on MUST be set to Enable.
Figure 4-28A: Advanced System Setup
Freq Conv Mode: Frequency Conversion Mode. Enable: output frequency is 50 Hz or 60 Hz, input frequency is 60 Hz or
50 Hz, UPS no alarm no battery and bypass abnormal. Default: Disable.
LBS Mode: Setting values: LBS disable, LBS master, LBS slave. Default: LBS disable.
Float Temp. Compen: Temperature sensor compensation switch. To connect a battery temperature sensor, change
the value to Enable (default is Disable).
Temp Sensor Select: Temperature sensor type selection. There are three options: OFF, NTC and RS485. Use NTC for
short distances of up to 16 feet (5 m) from the UPS. Use RS485 for multiple sensors and for distances of up to 65 feet
(20 m) from the UPS. Default is OFF.
Figure 4-28B: Advanced System Setup