Tripp Lite SMART1200PSGLCD 1200VA 720W 120V Pure Sine Wave Gaming UPS Battery Backup - LCD, AVR, RGB LEDs, USB Charging, Power Saving

Owner's Manual - Page 9

For SMART1200PSGLCD. Series: AG-052B
Also, The document are for others Tripp Lite models: SMART600PSGLCD, SMART1000PSGLCD, SMART1500PSGLCD

PDF File Manual, 72 pages, Read Online | Download pdf file

SMART1200PSGLCD photo
Loading ...
Loading ...
Loading ...
9
Note: If there is a power interruption while replacing the batteries, the load will not be
backed up even if the UPS is on. To replace the batteries with UPS on, start with step 5.
Follow the steps below to replace the battery.
Step 1: Turn off all equipment plugged into the UPS system’s outlets.
Step 2: Turn off the UPS.
Step 3: Remove the UPS system’s AC input plug from the AC wall outlet.
Step 4: Unplug all equipment from the UPS system’s outlets.
Step 5: Remove the battery cover by loosening
the two
screws
A
located on the bottom of the UPS
and slide the battery cover downward, then outward.
Step 6: Disconnect the battery wires
B
(BAT+ and BAT-).
Then, slide out the existing battery pack from the
UPS by grasping the battery tap.
Caution - Do NOT short the positive wire and negative wire of the battery.
Caution - DO NOT pull the battery pack out by pulling on the battery wires.
Step 7: Slide the new battery pack into the UPS.
Step 8: Verify proper polarity. Reconnect the battery connectors.
Note: Some sparking might occur. This is normal.
Step 9: Reinstall the battery cover. The UPS is ready for normal operation.
Note: Properly dispose of the old batteries at an appropriate recycling facility. Refer to your local codes for disposal requirements or in the
USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit tripplite.com/support/recycling-program/ for recycling
information.
6. Battery Replacement
A
BAT+
BAT-
B
B
Loading ...
Loading ...
Loading ...