40 | PERFORMANCE DATA
Single Zone High Efciency Standard Wall Mount Engineering Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
PERFORMANCE DATA
Heating Capacity
LS090HSV5, LS120HSV5
Outdoor Air
Temp.
Indoor Air Temperature (°F DB)
°F DB °F WB
60 64 68 70 72 75 86
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-3 -4 5.56 0.47 5.39 0.47 5.34 0.47 5.28 0.46 5.24 0.46 5.14 0.46 5.02 0.46
0 -1 6.05 0.52 5.87 0.51 5.81 0.51 5.75 0.51 5.71 0.51 5.59 0.50 5.46 0.50
1 0 6.13 0.53 5.94 0.52 5.88 0.52 5.83 0.51 5.78 0.51 5.66 0.51 5.53 0.51
6 5 6.40 0.54 6.21 0.54 6.15 0.54 6.09 0.53 6.04 0.53 5.92 0.53 5.78 0.53
10 9 6.69 0.56 6.48 0.56 6.42 0.56 6.35 0.55 6.31 0.55 6.18 0.54 6.03 0.54
16 14 6.90 0.57 6.69 0.56 6.62 0.56 6.55 0.56 6.50 0.56 6.37 0.55 6.22 0.55
17 15 6.94 0.57 6.73 0.57 6.67 0.57 6.60 0.56 6.55 0.56 6.42 0.56 6.26 0.56
19 17 7.04 0.58 6.82 0.58 6.76 0.58 6.69 0.57 6.64 0.57 6.50 0.57 6.35 0.57
24 23 7.72 0.61 7.49 0.60 7.41 0.60 7.34 0.59 7.28 0.59 7.13 0.59 6.96 0.59
32 30 9.25 0.65 8.97 0.65 8.88 0.65 8.79 0.64 8.73 0.64 8.55 0.64 8.35 0.64
41 38 10.62 0.70 10.30 0.69 10.19 0.69 10.09 0.68 10.01 0.68 9.81 0.68 9.58 0.68
43 40 10.96 0.71 10.63 0.70 10.52 0.70 10.41 0.69 10.33 0.69 10.13 0.69 9.89 0.69
47 43 11.47 0.72 11.12 0.72 11.01 0.72 10.90 0.71 10.82 0.71 10.60 0.70 10.35 0.70
53 50 11.58 0.73 11.23 0.72 11.12 0.72 11.01 0.72 10.92 0.72 10.71 0.71 10.45 0.71
59 53 11.85 0.74 11.49 0.73 11.37 0.73 11.26 0.72 11.17 0.72 10.95 0.72 10.69 0.72
64 57 12.10 0.75 11.73 0.75 11.61 0.75 11.50 0.74 11.41 0.74 11.18 0.73 10.92 0.73
70 61 12.33 0.76 11.96 0.76 11.83 0.76 11.72 0.75 11.63 0.75 11.39 0.74 11.12 0.74
75 65 12.50 0.77 12.12 0.77 12.00 0.77 11.88 0.76 11.79 0.76 11.55 0.75 11.28 0.75
Table 14: LSN090HSV5 / LSU090HSV5 Heating Capacities.
Outdoor Air
Temp.
Indoor Air Temperature (°F DB)
°F DB °F WB
60 64 68 70 72 75 86
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-3 -4 6.94 0.71 6.73 0.70 6.66 0.70 6.59 0.69 6.54 0.69 6.41 0.69 6.26 0.69
0 -1 7.55 0.78 7.32 0.77 7.25 0.77 7.18 0.76 7.12 0.76 6.98 0.75 6.81 0.75
1 0 7.65 0.78 7.42 0.78 7.34 0.78 7.27 0.77 7.21 0.77 7.07 0.76 6.90 0.76
6 5 7.99 0.81 7.75 0.80 7.67 0.80 7.59 0.80 7.54 0.80 7.38 0.79 7.21 0.79
10 9 8.34 0.84 8.09 0.83 8.01 0.83 7.93 0.82 7.87 0.82 7.71 0.81 7.53 0.81
16 14 8.61 0.85 8.34 0.84 8.26 0.84 8.18 0.83 8.12 0.83 7.95 0.82 7.76 0.82
17 15 8.66 0.85 8.40 0.85 8.32 0.85 8.23 0.84 8.17 0.84 8.01 0.83 7.82 0.83
19 17 8.78 0.87 8.52 0.86 8.43 0.86 8.35 0.86 8.28 0.86 8.12 0.85 7.92 0.85
24 23 9.63 0.90 9.34 0.90 9.25 0.90 9.15 0.89 9.08 0.89 8.90 0.88 8.69 0.88
32 30 11.55 0.98 11.20 0.97 11.08 0.97 10.97 0.96 10.89 0.96 10.67 0.95 10.42 0.95
41 38 13.25 1.04 12.85 1.03 12.72 1.03 12.59 1.02 12.49 1.02 12.24 1.01 11.95 1.01
43 40 13.67 1.06 13.26 1.05 13.12 1.05 12.99 1.04 12.89 1.04 12.64 1.03 12.34 1.03
47 43 14.31 1.08 13.88 1.07 13.74 1.07 13.60 1.04 13.50 1.06 13.23 1.05 12.91 1.05
53 50 14.45 1.09 14.02 1.08 13.87 1.08 13.74 1.07 13.63 1.07 13.36 1.06 13.04 1.06
59 53 14.78 1.10 14.33 1.09 14.19 1.09 14.05 1.08 13.94 1.08 13.66 1.07 13.34 1.07
64 57 15.10 1.12 14.64 1.11 14.49 1.11 14.35 1.10 14.24 1.10 13.95 1.09 13.62 1.09
70 61 15.38 1.14 14.92 1.13 14.77 1.13 14.62 1.12 14.51 1.12 14.22 1.11 13.88 1.11
75 65 15.60 1.16 15.13 1.15 14.97 1.15 14.82 1.13 14.71 1.13 14.42 1.12 14.07 1.12
Table 15: LSN120HSV5 / LSU120HSV5 Heating Capacities.
DB: Dry Bulb Temperature (°F) WB: Wet Bulb Temperature (°F) TC: Total Capacity (kBtu/h)
PI: Power Input (kW) (includes compressor,indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible. Do not extrapolate.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
60ºF wet bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Heating Capacity Table for LS090HSV5 (LSU090HSV5 + LSN090HSV5)
Heating Capacity Table for LS120HSV5 (LSU120HSV5 + LSN120HSV5)