Filling the Water Heater
Never use this water heater unless it is completely full of water.
To prevent damage to the tank and heating element, the tank
must be lled with water. Water must ow from the hot water
faucet before turning “ON” power.
To ll the water heater with water:
1. Close the water heater drain valve by turning the handle to
the right (clockwise). The drain valve is located on the lower
front of the water heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when
the water heater is in use.
3. To ensure complete lling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run until
a constant ow is obtained. This will let air out of the water
heater and the piping.
4. Check all new water piping for leaks. Repair as needed.
Converting the Lower Element
These instructions only cover the conversion of the convertible
element, read this entire manual before attempting to install
or operate the water heater. The water heater is factory set to
operate at 3800 watts. The lower element can be converted to
operate at 5500 watts. Refer to Facts to Consider About the
Convertible Lower Element section.
The Upper Element, (if double element model) is a conventional
3800 watt element which only operates at its rated wattage on
240 volts. (See rating plate on the water heater.)
The lower Element of the water heater can be converted from
operation at 3800 watts to 5500 watts on a 240 volt system.
If after reading these instructions and this manual, if you do not
understand any portion call Sears Service Center.
Before making the conversion to 5500 watts, make sure that the
(1) power supply is 240 volts, (2) the wiring is 10 gauge AWG
@ Type TW, 60°C or equivalent, and (3) the circuit breakers
or fusing are capable of 30 amp loading. Also, the installation
must conform with this manual, local codes and electric utility
rules. Failure to comply can result in DEATH, SERIOUS BODILY
INJURY, OR PROPERTY DAMAGE.
NOTE: Whether or not the element conversion is made the
model rating plate must be marked. Using a hard point ink pen,
check the appropriate block within the model rating plate, which
is located adjacent to the lower access panel.
FIGURE 11.
Necessary element conversion parts are located in a small bag
contained within the electrical junction box on top of the water heater.
FIGURE 12.
1. Before beginning the conversion turn “OFF” electric power
supply to the water heater.
FIGURE 13.
2. The convertible element is located behind the lower access
panel of the water heater. Remove the screw securing the
access panel, and remove panel.
FIGURE 14.