Page7
Version1.0Aug2018
Ref Item MinClearance
(Fanassisted)
(mm)
1 Beloweaves,balconiesandotherprojections:
Appliancesupto50MJ/hrinput 200
Appliancesover50MJ/hrinput 300
2 Fromtheground,aboveabalconyorothersurface* 300
3 Fromareturnwallorexternalcorner* 300
4 Fromagasmeter(M)
seeAS/NZS5601Cl.5.11.5.9forventterminallocationofregulator
seeAS/NZS5601Table6.7forNewZealandrequirements
1000
5 Fromanelectricitymeterorfusebox(P)^ 500
6 Fromadrainpipeorsoilpipe 75
7 Horizontallyfromanybuildingstructure*orobstructionfacingaterminal 500
8 Fromanyotherflueterminal,cowl,orcombustionairintake* 300
9 Horizontally from an openable window, door, non‐mechanical air inlet, or any other opening into a
buildingwiththeexceptionofsub‐floorventilation:
Appliancesupto150MJ/hrinput* 300
Appliancesover150MJ/hrinputupto200MJ/hrinput* 300
Appliancesover200MJ/hrinputupto250MJ/hrinput* 500
Appliancesoverto250MJ/hrinput* 1500
Allfan‐assistedappliances,inthedirectionofdischarge 1500
10 Fromamechanicalairinlet,includingaspablower 1000
11 Verticallybelowanopenablewindow,non‐mechanicalairinlet,oranyotheropeningintoabuildingwith
theexceptionofsub‐floorventilation:
‐ Forspaceheatersupto50MJ/hrinput 150
‐ Forotherappliancesupto50MJ/hrinput 500
‐ Forappliancesover50MJ/hrinputandupto150MJ/hrinput 1000
‐ Forappliancesover150MJ/hrinput 1500
*unlessapplianceiscertifiedforcloserinstallation
^prohibitedareabelowelectricitymeterorfuseboxextendstogroundlevel
Loading ...