Weil-McLain EGH COMMERCIAL GAS BOILER EGH-125 Commercial Gas Steam Boiler

User Manual - Page 23

For EGH COMMERCIAL GAS BOILER EGH-125.

PDF File Manual, 40 pages, Read Online | Download pdf file

EGH COMMERCIAL GAS BOILER EGH-125 photo
Loading ...
Loading ...
Loading ...
3DUW1XPEHU
23
For your safety, turn off electrical power supply at ser-
vice entrance panel before making any electrical con-
nections to avoid possible electric shock hazard. Fail-
ure to do so can cause severe personal injury or death.
Refer to the Control Supplement for additional
information, operating instructions and control
wiring diagram.
Wiring must be N.E.C. Class 1.
If rollout thermal fuse element wire supplied with
boiler must be replaced, type 200 °C wire or equiva-
lent must be used. If other original wiring supplied
with boiler must be replaced, use only type 105 °C
wire or equivalent.
Boiler must be electrically grounded as required
by National Electrical Code ANSI/NFPA 70–latest
edition.
Electrical installation must comply with:
1. National Electrical Code ANSI/NFPA 70–latest edition and any
other national, state, provincial or local codes or regulations.
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, and
any local codes
Wiring connections
1. Boiler is shipped with controls completely wired, except
spill switch and vent damper. See wiring diagram in Control
Supplement for details.
2. Installer must attach wiring diagram inside jacket door.
3. See Figure 26 for field wiring. A separate 120VAC electrical
circuit with a fused disconnect switch (15 amp recommended)
should be used for the boiler.
4. A strain relief bushing and adapter must be used at each point
where wiring passes through control case (see Figure 27) to
protect wiring insulation.
5. Multiple zones — Refer to zone valve manufacturer’s literature
for wiring and application. A separate transformer is required
to power zone valves. Zoning with circulators requires a relay
for each circuit.
Room thermostat
1. Connect thermostat as shown on wiring diagram on boiler.
2. Install on inside wall away from influences of drafts, hot or
cold water pipes, lighting fixtures, television, sunrays or fire-
places.
3. If thermostat has a heat anticipator, set heat anticipator in
thermostat to match power requirements of equipment con-
nected to it. Refer to the appropriate Control Supplement for
instructions on the thermostat anticipator setting.
&IGURE Provide strain relief
ConneFt Àeld ZLrLnJ to EoLler
&IGURE Connect field wiring in boiler junction box as shown below. See Control Supplement for more details.
DHW (if used)
Connect the DHW aquastat as shown in wiring below. The
Economy function of the control is not utilized with DHW
input.
R & C Connections (if used)
6!#LEADSSHOULDBEUSEDFORPOWERSTEALINGTHERMOSTATSONLY
Other devices requiring 24 VAC should have sepa-
rate power supply.
EG
&
PEG SERIES 5
s
EGH SERIES 5 GAS-FIRED BOILERSBOILER MANUAL
Loading ...
Loading ...
Loading ...