Maintenance
Owner’s Manual for 60 Hz Air-Cooled Generators 27
Checking Engine Oil Level
IMPORTANT NOTE: Verify oil level daily when power
outages necessitate running generator for extended
periods. Generator will shut down if oil level is low.
Proceed as follows to check engine oil level:
1. Set utility MLCB to OFF (OPEN).
2. Set generator MLCB (generator disconnect) to
OFF (OPEN).
3. Allow generator to run for a cool-down period of
approximately one minute, if generator was run-
ning during an outage.
4. Press OFF button to turn generator off. Wait five
minutes.
5. See Figure 2-1, Figure 2-2, or Figure 2-3.
Remove oil dipstick and wipe it dry with a clean
cloth.
6. Completely insert oil dipstick into oil dipstick tube
and remove.
7. Observe oil level. Oil level should be at FULL mark
on oil dipstick.
8. If necessary, remove oil fill cap and add recom-
mended oil to engine (with oil dipstick removed)
until oil level reaches FULL mark. Insert oil dipstick
and install fill cap. See Engine Oil Requirements.
To restart generator:
1. Press AUTO button on control panel.
2. Allow generator to start and warm up for a few min-
utes.
3. Set generator MLCB (generator disconnect) to ON
(CLOSED).
The system is now operating in AUTO. The utility MLCB
can be turned ON (CLOSED).
Engine Oil Requirements
Engine oil should be serviced in accordance with the rec-
ommendations of this manual to maintain product war-
ranty. Generac maintenance kits consisting of engine oil,
oil filter, air filter, spark plug(s), a shop towel, and a funnel
are available through an IASD.
All Generac oil kits meet minimum American Petroleum
Institute (API) Service Class SJ, SL, or better. Do not use
special additives.
Synthetic SAE 5W-30 for all temperature ranges. See
Engine.
Changing the Oil and Oil Filter
Proceed as follows to change oil and oil filter:
1. Lift lid and press MANUAL button on control panel
to start engine, and run unit until it is thoroughly
warmed up. Press OFF button on control panel to
shut down engine.
2. See
Figure 4-1, Figure 4-2, or Figure 4-3.
Remove front panel when unit has cooled. Pull oil
drain hose (A) free of retaining clip. Remove cap
from oil drain hose and place free end into a suit-
able container. Drain oil.
Figure 4-1. Oil Filter and Drain Location (10 kW)
(000139)
WARNING
Risk of burns. Allow engine to cool before
draining oil or coolant. Failure to do so could
result in death or serious injury.
(000210)
WARNING
Skin irritation. Avoid prolonged or repeated contact with
used motor oil. Used motor oil has been shown to cause
skin cancer in laboratory animals. Thoroughly wash
exposed areas with soap and water.
(000135)
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.
CAUTION
(000135)
Engine damage. Verify proper type and quantity of
engine oil prior to starting engine. Failure to do so
could result in engine damage.