13
Dr.PTAC information
e Dr. PTAC system is an add on system to our standard PTAC unit to provide conditioned makeup air into a space thru
the PTAC unit by providing up to 55 CFM of outdoor air 24/7 by forced fan and cycling dehumidier compressor based on
outdoor relative humidity levels.
Dr. PTAC was created to solve issues with dehumidication in rooms and to introduce fresh air due to deciencies of
oxygen levels. Dr. PTAC is not only a PTAC but a Conditioned Make Up Air unit. New ASHRAE studies show that many
illnesses in hotel rooms can be attributed to oxygen decient atmospheres. Dr. PTAC solves that issue by introducing tem-
pered conditioned make up air that satises both humidity level introduction and supplied oxygen.
Dr. PTAC is a two-stage system. e primary unit is responsible for control of Sensible Heat that is introduced into the
room via make up air temperature and thermal load of the occupants. e secondary unit is primarily a dehumidica-
tion unit that provides up to 55 CFM of outside fresh air into the room. e correction of the Sensible Temperature comes
from the main PTAC unit, which provides additional dehumidication with temperature correction. Overall unit e-
ciency over standard PTAC’s is approximately 3% improvement. e compressor/dehumidication process is controlled by
a humidistat (factory set at 50% RH), which is monitoring the outdoor relative humidity level and is adjustable by a quali-
ed servicer. When the outdoor humidity level raises above 50% RH, the compressor and dehumidication process starts.
Below 50% RH, compressor operation and dehumidication is stopped, however, fan operation continues to provide up to
55 CFM of outdoor air into the space.
e dehumidication system has a temperature switch which is monitoring both the refrigeration and the outdoor air
temperatures. If the outdoor air goes below 38 °F, the compressor is disabled with fan operation continuing to provide
outdoor air into the space. All dehumidier controls and safeties are automatically reset. An optional air tempering heater
is available for the fresh air system for applications where operation in cold winter climates is required. Condensate from
the dehumidier drains into the PTAC drain pan, where it is also slung onto the condenser coil for re-evaporation outside
when the A/C runs. Excess condensate is drained into the wall case, which can then either drain to the outside through the
louver OR is piped to a drainage system via an optional drain kit.
ADVANTAGES OF THE DR. PTAC SYSTEM:
1. Lower installation/renovation costs than typical DOAS*
2. Decrease inconvenience to customer due to construction/installation of a DOAS* system
3. More humidity control in a room over use of a simple PTAC vent or Power vent system
4. Allows fresh make up air to travel entirely across sleeping and living areas of a room, exiting through a duct or under
the door
*DOAS = Dedicated Outdoor Air System