OUTDOOR TECHNICAL OVERVIEW
B-23
ENGLISH
Topic TitleDIP Switch Settings
WJ26X25054 - Service Monitor Board DIP Switch Settings
Outdoor Central
Control Address
SW6-1 SW6-2 SW6-3 SW6-4
0 OFF OFF OFF OFF
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
9 ON OFF OFF ON
10 ON OFF ON OFF
11 ON OFF ON ON
12 ON ON OFF OFF
13 ON ON OFF ON
14 ON ON ON OFF
15 ON ON ON ON
Outdoor central control address settings
Definition SW1-1 SW1-2 SW1-3 SW1-4
Factory default OFF OFF OFF OFF
Forced heating ON OFF OFF OFF
Forced cooling OFF ON OFF OFF
Rated operation OFF OFF ON OFF
Time defrost valid: Defrost initiates if
needed when the compressor has been on
for 10 minutes continuously and 50 minutes
cumulative. Termination conditions are the
same as demand defrost.
OFF OFF OFF ON
Wiring check active* ON ON ON ON
Description SW7-1 SW7-2 SW7-3 SW7-4 SW7-5 SW7-6 SW7-7 SW7-8
USA energy efficiency test mode for High Wall unit OFF* OFF* ---- ---- ---- ---- ---- ----
USA energy efficiency test mode for Duct unit ON OFF ---- ---- ---- ---- ---- ----
Reserved ---- OFF* ---- ---- ---- ---- ----
Reserved ---- ---- ---- OFF* ---- ---- ---- ----
Reserved ---- ---- ---- ---- OFF* ---- ---- ----
Reserved ---- ---- ---- ---- ---- OFF* ---- ----
North American region ---- ---- ---- ---- ---- ---- ON* ----
Non-North American region ---- ---- ---- ---- ---- ---- OFF ----
Quiet operation valid ---- ---- ---- ---- ---- ---- ---- OFF*
SW6 DIP Switch Settings
SW1 DIP Switch Settings
SW7 DIP Switch Settings
*Factory Default Setting
*See page B-18 for Wiring Error Check.