System Operation
Water Quality Guidelines
A. The ultraviolet water filter is intended for the use with visually clear water, not colored, cloudy or turbid.
Ambient Water Temperature: 2-45
Iron: <0.3ppm (0.3mg/l)
Hardness: <7gpg (120mg/l)
Turbidity: <1NTU
Manganese: 0.05ppm (0.05mg/l)
UV Transmittance: >75%
B. Recheck the installation before plug the filter into power.
C. Do not proceed to install the equipment when UV Lamp or Sleeve Tube is broken, buy one again and continue.
D. Ultraviolet Water Treatment System is designed for continuous operation and frequent switching will reduce Ultraviolet radiation
and service life.
E. If this unit falls into the water, turn mainpower off and then retrieve it. Do not attempt to use this filter if it has been submerged.
F. Do not operate this unit if it has a damaged cord or plug, if it is malfunctioning or if it has been dropped or been damaged in any
manner.
Step 15Select a readily accessible and well lit location to fix the system. The system should always be located close to the
point of entry and can either be installed horizontally or vertically.
Step 16When all plumbing connections are finished, slowly turn on the water supply and check for leaks.
Step 17Allow the water to run for a few minutes to clear any air or dust that may be in the filter chamber.