©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Table 3: Multi F Outdoor Unit Electrical Data.
GENERAL DATA
Multi F Outdoor Unit Electrical Data
Nominal
Tons
Unit Model No. Hertz Voltage
Voltage
Range
(Min. to Max.)
MCA MOP
Compressor
Quantity
Compressor
Motor RLA
Outdoor Fan Motor
Indoor
Fan
Motor
kW FLA FLA
1.5 LMU180HV
60 208 - 230 187 - 253
15.8 20 1 12.0 0.085 0.40 0.40
1.5 LMU18CHV 13.3 20 1 8.9 0.09 0.59 1.60
2 LMU240HV 16.0 20 1 12.0 0.085 0.40 0.60
2 LMU24CHV 14.3 20 1 9.4 0.09 0.59 2.00
2.5 LMU30CHV 16.6 25 1 10.8 0.12 0.73 2.40
3 LMU36CHV 17.9 25 1 11.2 0.12 0.73 3.20
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance
is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Maximum Overcurrent Protection (MOP) is calculated as follows:
(Largest motor FLA x 2.25) + (Sum of other motor FLA) rounded
down to the nearest standard fuse size.
Indoor Fan Motor (FLA) is based on the maximum combination of
indoor units.
The max combination for each outdoor unit is:
- 18,000 ODU (LMU180HV / LMU18CHV): 12,000 IDU x 2
- 24,000 ODU (LMU240HV / LMU24CHV): 12,000 IDU x 2 + 9,000
IDU x 1
- 30,000 ODU (LMU30CHV): 12,000 IDU x 3
- 36,000 ODU (LMU36CHV): 12,000 IDU x 4