OPERATION (cont.)
Operating Modes
The Classic 40 and Classic 60 can be operated in two modes, FAN ONLY and
COOL. When in FAN ONLY mode, the unit circulates the surrounding air. When in
COOL mode, the compressor is operated and cool air is circulated.
1. COOL Mode
Once the compressor has been disengaged for more than 120 sec, the unit
operates in FAN ONLY mode for approximately 5 sec before the compressor
re-engages.
2. Temperature Control
The room temperature thermistor monitors the inlet temperature versus set
point temperature and switches the unit automatically between COOL and
FAN ONLY modes.
3. Fan Mode Control DIP Switch
The fan mode control DIP switch determines whether the fan continues to
operate or stop when the compressor cycles off. (Set point temperature below
the inlet air or room temperature.) The unit has been preset at the factory for
continuous fan operation.
Note: If you want to change the fan mode operation (from OPERATE to
STOP), contact your MovinCool reseller.
4. Temperature Scale Display
The temperature scale display changes the temperature(s) that are displayed
to either °C or °F. The unit has been preset from the factory to display the
temperature(s) in °F.
Note: If you want to change the temperature scale display (from °F to °C), hold
down the SET TEMP buttons ( / ) and the FAN button simultaneously for
3 sec.