Remington REM-45-KFA-B Kerosene Forced Air Heater

User Manual - Page 6

For REM-45-KFA-B.

PDF File Manual, 28 pages, Download pdf file

Loading ...
Loading ...
Loading ...
6
NEVER LEAVE HEATER UNATTENDED WHILE BURNING
OR WHILE CONNECTED TO A POWER SOURCE
© 2021 Pinnacle Climate Technologies, Inc. Kerosene Forced Air Heater User’s Manual
Fueling The Heater:
Kerosene (K-1)
For optimal performance of this heater, it is
strongly suggested that K-1 kerosene be used,
especially in temperatures lower than 26°F
(-3°C). K-1 kerosene has been refined to virtually
eliminate contaminants, such as sulfur, which can
cause a rotten egg odor during the operation of
the heater. Using diesel fuel can cause excess
soot production. Do not use Bio-Diesel as this fuel
will damage your heater’s seals and filter.
- CSA certified for use with K-1 kerosene, no.
1 & no. 2 diesel, JP8/Jet A Fuel, no. 1 and no.
2 fuel oil.
DO NOT use any fuel that is not approved above.
- NEVER use fuel such as, benzene, alcohol, white
glass, camp stove fuel, paint thinners, or other oil
compounds in this heater. THESE ARE VOLATILE
FUELS THAT CAN CAUSE A FIRE OR
EXPLOSION.
- NEVER store kerosene in the living space. Kerosene
should be stored in a well ventilated area outside
the living area.
- NEVER store kerosene in direct sunlight or near a
source of heat.
- NEVER use kerosene that has been stored from
one season to the next. Kerosene deteriorates
over time. OLD KEROSENE WILL NOT BURN
PROPERLY IN THIS HEATER.
NOTE: Kerosene should only be stored in a blue
container that is clearly marked “Kerosene.” Never
store kerosene in a red container. Red is associated
with gasoline.
Ventilation:
- Risk of indoor air pollution and Carbon
Monoxide Poisoning. Use heater only in well
ventilated areas.
- Refer to Safety Information on page 3 for
information about Carbon Monoxide
Poisoning.
- ALWAYS provide a fresh air opening in the heated space
of at least three square feet (2,800 sq. cm) for each
100,000 Btu / Hr. (29 kW) of heater output. Provide a
larger opening if more heaters are being used.
Minimum Ventilation Opening Needed
45-KFA 80T-KFA 140T-KFA
1.4 ft.² 2.4 ft.² 4.2 ft.²
1300 cm² 2230 cm² 3902 cm²
Minimum Ventilation Opening Needed
175T-KFA 215T-KFA
5.3 ft.² 6.5 ft.²
4924 cm² 6039 cm²
OPERATION
NEVER FILL
THE FUEL TANK
INDOORS. AL-
WAYS FILL THE TANK OUTDOORS. BE
SURE THAT THE HEATER IS ON LEVEL
GROUND WHEN FUELING, AND NEVER
OVERFILL THE TANK.
CAUTION
CARBON MONOXIDE POISONING MAY
LEAD TO DEATH!
DANGER
DO NOT USE
GASOLINE OR
CRANKCASE
DRAININGS.
WARNING
NEVER REFUEL
THIS HEATER
WHILE IT IS HOT
OR OPERATING. FIRE OR EXPLOSION
COULD RESULT.
DANGER