Installation Instructions
265 VOLT ELECTRICAL CONNECTION OPTIONS
./k WARNING:
Connection of this 265 V AC product to a branch circuit
MUST be done by direct connection in accordance with
the National Electrical Code. Plugging this unit into a
building mounted exposed receptacle is not pemfitted
bv code,
These models must be installed using the appropriate
GE power supply kit tor the branch circuit amperage
and the electrical resistance heater wattage desired.
Use the PO_4'ER CONNECTION CHART on page 17
to detemfine the correct kit required, One of the
following installation methods (A or B) I//tlSt be used.
A. FOR SUBBASE INSTALLATION
Electrical subbase !dts are available to provide a flexible
enclos/li'e Ik)i" direct connection.
Branch Circuit and Proper GE Power
UnitAmperage Bating Subbase Kit SupplyKit
15 ILML204E 15 I_M(5172
20 ILML204E20 I_M(5202
30 IL_K204E30 ILM(5302
The instructions provided with the selected subbase kit
must be carelifllv tollowed. It is the responsibility of the
installer to ensure the connection of components is
done in accordance with these instructions and all
electrical codes.
B. FOR DIRECT CONNECT
INSTALLATION
If an electrical subbase is not used, direct connection to
branch circuit wiring inside the provided junction box
must be done in accordance with the tollowing steps.
Order the t011owing Kit tiw 265 volt direct connection as
required:
Branch Circuitand Power
UnitAmperage Rating SupplyKit
15 1_M(5157
20 1_I(5207
30 1_K5307
Proceed to the "MAIZE EI,ECTRICM, CONNECTION
TO THE UNIT" section.
15