NOTE:
NEVER TRANSPORT OR TURN THE APPLIANCE UPSIDE DOWN OR ON ITS SIDE. IF THISOCCURS,
WAIT 6 HOURS BEFORE TURNING THE APPLIANCE ON, 24 HOURS IS RECOMMENDED. After the
unit has been on its side, oil needs to return to the compressor to ensure proper function. With-
out allowing the unit this time (6-24 hours) the unit may function for only a short time, and then
the compressor will break down from lack of oil.
TROUBLESHOOTING
PROBLEM CAUSE REMEDY
The air o No electricity, o Restore electricity.
conditioning unit _ It is not plugged into the outlet. _ Plug into the outlet.
does not start, o The safety device of the plug has o Reset the safety plug.
tripped.
o The internal safety device has tripped. Wait 30 minutes, if the pro-
blem persists, contact your
service center.
The air o The air exhaust hose has a constriction, o
conditioning unit
works for a short o The air exhaust hose is blocked, o
time only.
o There are tight bends in the air exhaust
hose.
Position the exhaust hose
correctly.
Check there are no
obstacles Obstructing air
discharge.
Eliminate the tight bends.
The air _ Window open.
conditioner _ There are heat sources in the room
works, but does (lamps, etc,).
not cool the o The exhaust hose is detached.
room. o Air filters clogged.
Close the window.
Eliminate the heat source.
o Connect the exhaust hose.
o Clean or replace the filters.
Bad odor in the o The filter is clogged.
room.
Clean or replace the filter.
The air
conditioner does
not operate for
about 3 minutes
after turning it on.
The internal compressor safety device
prevents the appliance from being
restarted until three minutes have ela-
psed since it was last turned off.
Wait. This delay is part of
normal operation.
Lk /PF/Fk
appears on the
display.
The appliance has a self diagnosis . See the self-diagnosis chap-
system to identify a number of malfunc- ter.
tions.