Series 2 Wall Mount Gas-fired Water Boiler Boiler Manual
37 Troubleshooting(continued)
Figure 118฀฀฀฀฀(continued)
Fault
Code
Fault Condition Correction
A01
No burner ignition
No gas
Check the regular gas ow to the boiler and that
the air has been eliminated from the pipes.
Ignition/detection electrode fault
Check the wiring of the electrode and that it is
correctly positioned and free of any deposits
Electrode fault
Check the ignitor electrode wiring
Electrode deformed/misaligned and/or improper
gap (5/32”)
Combustion incorrect
Natural gas & LP fuel
Perform combustion test for Natural gas & LP
fuel per chart section Figure 107, page 82 and
Figure 110, page 83.
Faulty gas valve Check the gas valve and replace it if necessary
Insufcient gas supply pressure Check the gas supply pressure
Condensate trap blocked and or con-
densate drain hose looped making a
second trap
Check the trap and clean it if necessary
Also inspect gas valve, blower, venturi, igniter,
and heat exchanger, and replace those with
signs of damage.
A02
Flame present signal
with burner off
Electrode fault
Check the ignitor electrode wiring
Electrode deformed/misaligned and/or improper
gap (5/32”)
Ignition cable fault Check the ignition cable
A03
Over temperature pro-
tection activation
Heating sensor damaged
Check the correct positioning and operation of
the heating sensor
No water circulation in the system Check the circulating pump
Air in the system/heat exchanger Vent the system/purge heat exchanger
A04
Exhaust duct safety
device activation
Fault F07 generated 3 times in the last
24 hours
See fault F07
A05
Fan protection activated
Fault F15 generated for 1 hour (con-
secutive)
See fault F15
A06
No ame after igni-
tion stage (6 times in 4
minutes)
Ignitor electrode fault
Check the position of the ignitor electrode and
replace it if necessary
Flame unstable Check the burner
Gas valve Offset fault Check the Offset adjustment at minimum power
Air/fume ducts obstructed
Remove the obstruction from the ue, exhaust
ducts and air inlet and terminals
Condensate trap blocked
Check the trap and clean it if necessary
Also inspect gas valve, blower, venturi, igniter,
and heat exchanger, and replace those with
signs of damage.
F07
High exhaust tempera-
ture
Air trapped in boiler heat
exchanger
Combustion not correct
for Natural gas and LP
fuel
Boiler water piping and
circulator not providing
correct water ow
The exhaust probe detects an excessive
temperature
Check the exchanger
Purge out air in heat exchanger
Check combustion per specication charts
Figure 107, page 82 and Figure 110, page 83.
Check piping sizes and required pump models
F10
Supply sensor 1 fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted
Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sensorWiring shorted
Wiring disconnected