2) WallPlenumandArchitecturalLouverInstallation
A, Install the wall plenum (VPAWP1-8/1-14) components in accordance with the installation instructions provided with each accessory,
O IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL
LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES
PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.
B, Ensure that the divider is adjusted propedy for the depth of the wail in accordance with the accessory installation manual
Figure5
WallPlenum& OutdoorLouverInstallation
Proper Flashing
Proper Header Caulk all 8
flange corners
Proper Caulking_
InsideWall Plenum
(Part B)
ProperCaulking
Architectural louver VPAL2 mounted
on the outside wall plenum (Part A)
Proper Flashing
Rough opening dimension 24 %" widex 307/8"high,
Ensurethat the bottom of the plenum is3/4"from the floor of the closet,
For proper airflow, maintain a minimum distance of 12" between Vert-I-Pak units (see Figure 1,page 3),
Consult the factory for any installation or application questions.