Friedrich VEA18K25RTG single-package vertical air conditioner

User Manual - Page 11

For VEA18K25RTG.

PDF File Manual, 16 pages, Download pdf file

Loading ...
Loading ...
Loading ...
920-075-07(10-03)
5) DuctworkPreparation
1) Duct ESP:
To determine your system's indoorexternal static pressure
(ESE in inches of water) use a duct calculator (as provided
by your duct supplier). Include all flex duct transitions and
discharge grille(s). If flex duct is used, be sure all the slack
is pulled out of the flex duct. Flex duct ESP can increase
considerably when not fully extended. DO NOT EXCEED a
total of .30 ESP,as this isthe MAXIMUM design limit for the
VERT-I-PAK A-Series unit.
2) Determining the Indoor CFM: Chart A - CFM
18000 12000/9000
.00 520 420
.10 510 410
.20 500 370
30 490 330
3) Correct CFM (if needed):
Chart B- Correction Multipliers
230V 1.00
208V 0.97
Heating 1.00
Cooling 0.95
6) ChassisInstallation
Install the followingcomponents as shownin Figure 5.
A,
B.
C.
Ensurethat thewallplenumis installedinaccordance with
the VPAWP1-8/1-14 Installation Manual,
Place the chassis intothe closet with the outdoor side
facing thewall plenum opening.
Slide the chassis intothe wall plenum until the plenum
divider seal isestablished. (See Figure 9)
Figure9
Slide-in View/Chassis Installation
/
TheVert-I-Pakchassismustbeinsertedintothewailplenumsothatthe
plenumdividergasketmakescontactwiththeplasticcondenserbaffleon
the unit.The chassiswill fit approximately23H'intothe wallplenum.
11