15
+
+
PUSH
BUTTON
DOOR STRIKE
MAGLOCK
PROXIMITY
SENSOR
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
Power for Door Strike
(Not Provided)
REQUEST TO EXIT
REQUEST TO EXIT (REX)
GROUND (BLACK GND)
POWER
GROUND
DATA 0 (GREEN DATA0)
DATA 1 (WHITE DATA1)
GROUND
SUPERVISED
GROUND (GND)
SUPERVISED
NORMALLY OPEN (N.O)
COMMON (COM)
NORMALLY OPEN (N.O.)
COMMON (COM)
NORMALLY CLOSED (N.C.)
NORMALLY OPEN (N.O.)
COMMON (COM)
NORMALLY OPEN
COMMON
NORMALLY CLOSED
COMMON
OR
OR
REQUEST TO EXIT
POWER
POSTAL LOCK**
*PRIMARY RELAY
ALARM BYPASS
NORMALLY OPEN
COMMON
AUXILIARY RELAY
ETHERNET CONNECTION
OR
NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
NOTE: For KPR2000 keypad
wire the pink and black (ground)
wires together.
READER
OR
KEYPAD
12 VDC POWER SUPPLY
WIEGAND
LIGHT
LOAD
LINE
NEUTRAL
Isolation
Relay
Low
Voltage
Power
Supply
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) or
equivalent
For AC Power:
Install a Siemens
S10K30MOV
(Metal Oxide Varistor) or
equivalent
* NOTE: MAGLOCK, door strike and
ALARM BYPASS not evaluated by UL.
NOTE: DO NOT
connect high
voltage power
to the CAPXS
unit.
POSTAL LOCK
** NOTE: For more information on how
to wire in a postal lock, refer to the
manual for accessory: CAPXSTKPL.
SUPERVISED
(DOOR STATUS)
DOOR SENSOR
(SUPERVISED)
DOOR SENSOR
(NON-SUPERVISED)
OR
EOL (End of Line) Resistor
(1k ohm)
Door Access
Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access.
ACCOUNT SETUP NETWORK/MOUNTINGPOWER ACCESS CONTROLINTRODUCTION
INTRODUCTION ACCOUNT SETUP NETWORK/MOUNTINGPOWER ACCESS CONTROL
INTRODUCTION ACCOUNT SETUP NETWORK/MOUNTINGPOWER ACCESS CONTROL
INTRODUCTION ACCOUNT SETUP NETWORK/MOUNTINGPOWER ACCESS CONTROL
INTRODUCTION ACCOUNT SETUP NETWORK/MOUNTINGPOWER ACCESS CONTROL
DO NOT INSTALL THE
SYSTEM IN THE FAIL
SECURE MODE UNLESS
PERMITTED BY THE LOCAL
AUTHORITY HAVING
JURISDICTION. Doing so
may cause interference with
the operation of panic
hardware.