OPERATIONS MANUAL
REFRIGERATED BASES & PIZZA PREP TABLES
6. Each system should be charged with the refrigerant type
as specified on the cabinet data tag. This refrigerant type
should match the type listed on the condensing unit being
used. The refrigerant charge should be held to the mini-
mum required for the satisfactory pull down and opera-
tion. For an accurate indication of refrigerant charge, the
sight glass will show a full column of liquid.
7. The superheat reading taken 6” from the compressor suc-
tion valve should be 30° +/- 5°. Expansion valve adjust-
ment may be necessary to achieve this superheat.
8. Installation of the electric condensate heater is the
responsibility of the installer (see “Installing Electric
Condensate Heater” under “Optional Accessories”).
CAUTION: EXTREME CARE MUST BE USED WHEN
ACCESSING THE SYSTEM DURING INSTALLATION. DUE
TO THE COMPLEXITY OF REMOTE REFRIGERATION
SYSTEMS AND THE POTENTIAL FOR IMPROPER
INSTALLATION, ANY RESTRICTIONS, LEAKS, FAILED OR
DAMAGED COMPONENTS CAUSED BY CONTAMINANTS
ARE NOT THE RESPONSIBILITY OF CONTINENTAL
REFRIGERATOR.
FISH FILE BASE MODELS
Fish File models are provided with drawers specially designed
for the storage of fresh fish, or similar product, packed in
crushed ice. Each drawer has a removable pan, with a drain
tube at the back corner (see Figure 18). Water from melting ice
in the pan, along with moisture from the product, drains out of
the storage pan through the tube, along a trough on the interior
cabinet wall, down to the sloped interior bottom, and out of the
cabinet through a 1” drain tube.
INSTALLATION AND LOCATION
In addition to normal considerations (see Installation and
Location), Fish File units should be installed directly over a
building floor drain, to rapidly dispose of water from melted ice
that drains out of the cabinet. It is also highly recommended that
your Fish File is located near a water source that can be used to
thoroughly wash down your cabinet regularly.
NOTE: If a building floor drain is not immediately avail-
able, a waste line, with consistent downward slope, must
be supplied and connected to the 1” NPS drain tube
located under the cabinet. An electric condensate vapor-
izer cannot be used to dispose of water from melted ice,
as the liquid waste contains food residue that can cause
unpleasant odors and potentially unsanitary conditions.
FIGURE 18: Fish File Drawer Assembly
MOUNTING
CAGE
GRATE
STORAGE
PAN
DRAIN
TUBE
DRAWER
SLIDE
DRAWER
ASSEMBLY