GENERAL DATA
Electrical Low-Static Ducted L1/L2/L3 Chassis
Table 12: Low-Static Ducted L1/L2/L3 Chassis Electrical Data.
Model Voltage Range MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
L1 Units
ARNU073L1G4
208-230
0.5
15
0.4
60 208-230 1
40 40
ARNU093L1G4 0.5 0.4 40 40
L2 Units
ARNU123L2G4
208-230
1.0
15
0.76
60 208-230 1
85 85
ARNU153L2G4 1.0 0.76 85 85
ARNU183L2G4 1.0 0.76 85 85
L3 Units
ARNU243L3G4 208-230 1.2 15 0.97 60 208-230 1 115 115
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.
Table 13: Vertical Air Handler NJ/NK Chassis Electrical Data.
Model Voltage Range MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
NJ Units
ARNU123NJA4
208-230
1.4
15
1.12
60 208-230 1
228 228
ARNU183NJA4 1.4 1.12 228 228
ARNU243NJA4 1.4 1.12 228 228
ARNU303NJA4 1.4 1.12 228 228
ARNU363NJA4 1.4 1.12 228 228
NK Units
ARNU423NKA4
208-230
2.3
15
1.8
60 208-230 1
366 366
ARNU483NKA4 2.3 1.8 366 366
ARNU543NKA4 2.3 1.8 366 366
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Instead of fuse, use circuit breaker.