GENERAL DATA
Electrical Low-Static Built-In B3/B4 Chassis
Table 11: Low-Static Built-In B3/B4 Chassis Electrical Data.
Model Voltage Range MCA MOP Rated Amps (A)
Power Supply Power Input (W)
Hz Volts Phase Cooling Heating
B3 Units
ARNU073B3G4
187-253
1.0
15
0.76
60 208-230 1
85 85
ARNU093B3G4 1.0 0.76 85 85
ARNU123B3G4 1.0 0.76 85 85
ARNU153B3G4 1.0 0.76 85 85
B4 Units
ARNU183B4G4
187-253
1.2
15
0.97
60 208-230 1
115 115
ARNU243B4G4 1.2 0.97 115 115
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.