FOR YOUR SAFETY, you must provide the openings listed
below for drainage, replacement air, and cross-ventilation
of any storage area exposed to possible leakage from gas
connections, the unit, or propane cylinders.
One side of the enclosure can be left completely open to
the outside, OR 4 ventilation openings must be created:
NATURAL GAS INSTALLS
Two of the openings are to be at the top level (approx. 4"
below the countertop) and on opposite walls of the enclosure.
2 more openings must be at the fl oor level (approx. 5" above
the fl oor) and on opposite sides of the enclosure. Each
opening must have a minimum of 10 sq. in. of free area.
To achieve the proper ventilation, you may drill a series of
holes, omit the grout from masonry joints, or replace a brick
with a hardware cloth screen. If the fl oor in the cabinet is
raised and the space beneath the cabinet is open to the
outside, the lower ventilation openings may be in the fl oor.
Reference Fig. 12-1.
PROPANE GAS INSTALLS
Two of the openings are to be at the cylinder valve level
(approx. 16" above the fl oor) and on opposite walls of
the enclosure. 2 more openings must be at the fl oor level
(approx. 5" above the fl oor) and on opposite sides of the
enclosure. Each opening must have a minimum of 10 sq.
in. of free area. To achieve the proper ventilation, you may
drill a series of holes, omit the grout from masonry joints,
or replace a brick with a hardware cloth screen. If the fl oor
in the cabinet is raised and the space beneath the cabinet
is open to the outside, the lower ventilation openings may
be in the fl oor. Reference Fig. 12-1.
WHEN A PROPANE CYLINDER IS USED
When a propane cylinder is installed inside of the enclosure,
the guidelines below MUST be followed. FAILURE TO
DO SO MAY CAUSE DAMAGE TO YOUR UNIT AND/OR
PERSONAL INJURY. Reference Fig. 12-2 for an example.
Only a C.S.A. listed stainless steel connector can be
connected to the grill.
The regulator/hose assembly coming from the propane
cylinder can only be connected to the above mentioned
grill fl ex connector. DO NOT connect the regulator/
hose assembly directly to the grill. An adapter will
be required.
A heatshield must be installed to protect the regulator/
hose assembly and propane cylinder valve.
Fire Magic offers a propane cylinder door with tank
tray to meet the cylinder install requirements. See
Fig. 12-3.
Fig. 12-2 Propane cylinder orientation
Fig. 12-1 Ventilation detail
Nat. gas
installs
(repeat for
opposite
side)
Fig. 12-3 Optional Fire Magic door w/tank tray
Adapter
L.P. gas
installs
(repeat for
opposite
side)
Grill
C.S.A. listed
stainless steel
ex connector
Heatshield
Regulator/
hose
assembly
L.P.
cylinder
Cylinder & regulator/
hose assembly
protected by heatshield
Equipped with
adapter for hose
assembly and
ex connector
ENCLOSURE REQUIREMENTS
REV 4 - 1401150550