GE - General Electric RAK150VF2 Wall Thermostat - Non-Programmable for AZ9V series (Phase 2)

User Manual - Page 10

For RAK150VF2.

PDF File Manual, 32 pages, Download pdf file

Loading ...
Loading ...
Loading ...
10
CONFIGURATION MODE
The configuration mode is used to set the RAK150VF2 to match
the heating/cooling system. The default setting of this thermostat
is for 2-stage cooling with a 3-stage heat pump system. For
an alternate configuration, see #7 in the Configuration Mode
Settings below.
To configure the RAK150VF2, perform the following steps:
1. Ensure thermostat is in OFF mode.
2. Remove the thermostat’s front cover.
3.
To enter the configuration mode, hold CONFIG for ~ 2 seconds.
4.
Once in the configuration mode, press the
<
or
>
button to
change settings within each screen.
- Press the FAN (right) button to advance to the next screen.
- Press the MODE (left) button to return to the previous screen.
NOTE: Hold CONFIG button for ~2 seconds to save changes
and exit configuration menu.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1.
Temperature Scale (°F or °C)—Choose Fahrenheit or Celsius.
- Press the
<
or
>
button to select.
- Press the FAN (right) button to advance to the
next screen. NOTE: Default factory setting is
Fahrenheit.
2.
Temperature Differential—Stage 1—(1–9°F) (.5-4.5°C)
Set the number of degrees between the “setpoint” temperature
and the “turn on” temperature for first stage.
- Press the
<
or
>
button to set differential
value.
- Press the FAN (right) button to advance to the next screen.
Note: Default factory setting is 1ºF /.5ºC.
3. Temperature Differential—Stage 2 (1–9°F) (.5-4.5°C)
Set the number of degrees between when stage 1 turns on
and stage 2 turns on.
- Press the
<
or
>
button to set differential
value.
- Press the FAN (right) button to advance to the next screen.
- Note: Default factory setting is 1°F/.5°C.
:
: