Majestic MONTANA36 Direct Vent Woodburning Fireplace

User Manual - Page 10

For MONTANA36.

PDF File Manual, 44 pages, Download pdf file

Loading ...
Loading ...
Loading ...
Outdoor Lifestyles by Hearth & Home Technologies • Montana US-CAN • 4039-156 Rev R • 09/19/13
10
C. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the replace opening. See Figure 3.4.
If you are using a decorative surround constructed of combustible material, it must be located within the shaded area de-
ned in Figure 3.3. Short stub walls are also acceptable if they are contained within the shaded area.
D. Frame the Fireplace
Figure 3.5 shows a typical framing (using 2 x 4 lumber) of the replace, assuming combustible materials are used. All re-
quired clearances to combustibles around the replace must be adhered to. See Figure 3.2. Any framing across the top of
the replace must be above the level of the top standoffs.
14-3/8 in./36.5 cm
12 in.
30.5 cm
39
deg.
4 in./10.2 cm
BRICK
FRONT
FLUSH FRONT
12 in.
30.5 cm
9-3/4 in./24.8 cm
50
deg.
A
B
Cat # A B
MONTANA-36 & 36H 36 in./91.4 cm 42 in./106.7 cm
MONTANA-42 & 42H 42 in./106.7 cm 48 in./121.9 cm
Figure 3.4 Sidewalls and Surrounds
Figure 3.5 Framing the Fireplace
2 in./51 mm
minimum air
space clearance
to the enclosure.
Use only noncombustible
material below the top of
the top standoffs.
24-1/8 in.
61.3 cm
42-3/8 in.
107.6 cm
A
CAT. # A
MONTANA-36 & 36H 43 in./109 cm
MONTANA-42 & 42H 49 in./124 cm