30
BSC Installation and Operation Manual
TROUBLESHOOTING
No Display, or Garbled Display
&KHFNWKH9$&SRZHULQSXWWRWKH%6&7XUQSRZHUWRWKH%6&RIIDQGEDFNRQ0DNHVXUH
that the Ground screw is connected to a reliable Earth Ground. Make sure that all wiring is fed
to the control through the bottom knockouts and that no high voltage wiring is running behind
the control board.
SENSOR INPUTS
Display shows Sensor OPEN or SHORT
When the reading is OPEN, Check the sensor is connected and the wires are continuous to the
BSC. Finally follow the procedure for Incorrect Temperature or Pressure Display. When the
reading is SHORT , remove the wires from the sensor terminals. The display should change to
read OPEN. If it does not, the BSC may be damaged.
Display shows an Incorrect Temperature
Remove the wires from the sensor terminals. The display should change to read OPEN. If it
does not, the BSC may be damaged. Take an ohm reading across the detached sensor wires. The
ohm reading should correspond to the Temperature sensor Table. If it does not, the sensor may
be damaged.
Display shows an Incorrect Pressure
,IWKHUHDGLQJLVDVSHFL¿HGDPRXQWDERYHRUEHORZWKHDFWXDOSUHVVXUHDGMXVWLWXVLQJWKH6\VWHP
Trim. If the reading is SHORT, remove the wires from the sensor terminals. The display should
change to read OPEN. If it does not, the BSC may be damaged.
CONTROL OPERATION
No Heat
 3URYH(YHQWKRXJKWKHV\VWHPUHOD\PD\EHHQHUJL]HGWKH%6&ZLOOQRWHQHUJL]HDQ\VWDJH
relays unless the Prove is shorted. Check Message Display Line on page 12.
 6KXWGRZQ- The BSC will activate stage outputs when the Shutdown terminals are short. Check
Message Display Line on page 12.
 6HQVRU)DXOW- When the Sensor Fault is set to Shutdown in the startup menu on page 7, the
System sensor fault (in all Sensor Type modes) or the Outdoor sensor fault (in Reset mode) will
GHHQHUJL]HDOOVWDJHUHOD\V&KHFNWKHGLVSOD\IRUVHQVRUYDOXHV
 6\VWHPRU2XWGRRU6HQVRU- If the System or Outdoor sensor reading was higher that the
DFWXDOWHPSHUDWXUHWKH%6&PLJKWQRWEULQJDQ\VWDJHRQ&KHFN'LVSOD\VKRZVDQ,QFRUUHFW
7HPSHUDWXUHVHFWLRQ
Too Much Heat
&KHFNLIWKHFRQWUROKDVDQ\RIWKHIROORZLQJ
 5HVHW5DWLRDQG2IIVHW- If excessive heat occurs only in certain weather conditions, adjust the
5HVHW5DWLRDQG2IIVHW6HH8QGHUVWDQGLQJ2SHUDWLQJ&RQFHSWRQSDJH5). If excessive heat occurs year round, reduce the Offset.
 %RLOHU0RGH6HWWLQJV- The BSC will only modulate boilers their mode is set to Auto or Standby. Check to if any boiler stage is set
to Manual or On. See Mode on page 24.
 &RQWURO6HWWLQJV7KH/DVW6WDJH+ROGZLOODOORZRQO\WKH/HDGERLOHUWRVWD\RQIRUDQDGGLWLRQDOQXPEHURIGHJUHHV,IWKH
VHWWLQJLVWRRKLJKDQGRQO\WKH/HDGERLOHULVRQWKHV\VWHPFDQRYHUKHDW5HGXFHWKH/DVW6WDJH+ROGVHWWLQJ6HHSDJH21.
Temperature Sensor Chart
TEMPERATURE
(in Degrees °F)
Value
(in Ohms)
-30 117720
-20 82823
-10 59076
0 42683
10 31215
20 23089
25 19939
30 17264
35 14985
40 13040
45 11374
50 9944
55 8714
60 7653
70 5941
80 4649
90 3667
100 2914
110 2332
120 1879
130 1524
140 1243
150 1021
160 842
170 699
180 583
190 489
200 412
210 349
220 297
230 253
240 217
250 187