Installation
English
Connecting to a Load
WARNING
SHOCK HAZARD!
Before proceeding further, carefully
check that the Inverter is NOT connected
to any batteries, and that all wiring is
disconnected from any electrical sources.
Make sure the bypass AC input plug is
disconnected to any AC source.
Do not connect the output terminals of the
Inverter to an incoming AC source.
Make sure the power switch is in off
position before and after the installation.
Neutral Grounding:
The neutral conductor of the AC output circuit
of the inverter is automatically connected to
the safety ground during inverter operation.
This conforms to National Electrical Code
requirements that a derived AC source, such
as an inverter or generator, must have their
neutral conductors tied to ground in the
same way that the neutral conductor from
the utility is tied to ground at the AC breaker
panel. When AC utility power is present and
the inverter is in bypass mode, this neutral to
ground connection is not present. The utility
power neutral is only connected to ground at
the breaker panel.
Ground Fault Circuit Interrupters
(GFCI):
Recreational Vehicles Installations (for
North American approvals) will require GFCI
protection. All branch circuits connected
to the AC output hard wire should be GFCI
protected. Additional electrical codes may
require GFCI protection of certain receptacles
in residential installations.
While the pure sine wave output of the
inverter is equivalent to the waveform
provided by utilities, compliance with
UL standards requires Furrion to test
and recommend specific GFCI. Use only
GENERAL PROTECT GROUP INC, Type DG15
ground-fault circuit-interrupter receptacles.
Or AMERICAN ELECTRIC DEPOT INC, Type
G1501 ground-fault circuit-interrupter
receptacles. Other types may fail to operate
properly when connected to this unit.
Hard-wire Installation
The AC wiring compartment is located on the
front panel of the inverter.
1. Remove the AC wiring compartment cover
to gain access to the AC output hard-wire
(pigtails leads). (Fig. 3)
Fig. 3
2. Remove the metal wire clip from the
cover. (Fig. 4)
Fig. 4