Dimplex ECSI100-580 100L Indirect Cylinder

User Manual - Page 12

For ECSI100-580.

PDF File Manual, 40 pages, Download pdf file

Loading ...
Loading ...
Loading ...
Installat
ion and User Instructions R
01127
-
2 06
/11
Page 12
Pre
-
Installation
Table 3: Sizing of copper discharge pipe “D2” for common temperature relief valve outlet sizes
4.4.2 Worked example
This example is for a temperature
relief valve with a discharge pipe (D2)
(as fitted on 125 to 300L cylinders)
having 4 No. 22mm elbows and length
of 7m from the tundish to the point of
discharge.
From Table 3, the maximum
resistance allowed for a straight
length of 22mm copper discharge pipe
(D2) from a temperature relief
valve is 9.0m. Subtract the resistance
for 4 No. 22mm elbows at 0.8m each
= 3.2m.
Therefore the maximum permitted
length
equates to 5.8m, which is less than
the actual length of 7m, therefore
calculate the next largest size.
Maximum resistance allowed for a
straight length of 28mm copper
discharge pipe (D2) from a G½
temperature relief valve is: 18m
Subtract the resistance for 4 No.
28mm elbows at 1.0m each = 4m
Therefore the maximum permitted
length equates to 14m.
As the actual length is 7m, a 28mm
(D2) copper pipe will be satisfactory.