PELLET VENT TERMINATION CLEARANCE
The stove vent must terminate on the outside of the building. Horizontal terminations must extend a
minimum of 12" from the wall. Vertical terminations must protrude a minimum of 24" from the roof
surface.
In addition, all clearances listed below must be met. SEE FIGURE 8
Must have an approved cap (to prevent water from entering) or a 45 degree downturn with rodent
screen.
If the termination is located on a windy side of the house, we suggest using an approved house shield
to prevent soot from building up on the side of the house.
A vent must not be located where it may become plugged by snow or other material.
Figure 8: Vent Termination
A: Minimum 48" clearance below or beside any door or window that opens. (This clearance may be
reduced to 18" if using outside air). We recommend the door or window be kept closed during operation.
Minimum 12" clearance below or beside any window that does not open.
B: Minimum 12" clearance above any door or window that opens.
C: Minimum 24" clearance from any adjacent building.
D: Minimum 7' clearance above any grade, when adjacent to public walkways.
E: Minimum 24" clearance above any grass, plants, or other combustible materials.
F: Minimum 36" clearance from any forced air intake of another appliance.
G: Minimum 24" clearance below eaves or overhangs.
H: Minimum 12" clearance horizontally from combustible wall.
X: Must be a minimum of 24" above the roof.
NOTE: May not vent into covered walkway or breezeway.