www.dimplex.de 452234.66.02 · FD 9311 EN11
English
SI 50TE - SI 130TE
12 Equipment Data
1 Type and order code
SI 50TE SI 75TE SI 100TE SI 130TE
2Design
2.1 Controller Internal Internal Internal Internal
2.2 Installation location / degree of protection according to EN 60 529 Indoors / IP 21 Indoors / IP 21 Indoors / IP 21 Indoors / IP 21
2.3 Performance levels 2222
3 Operating limits
3.1 Heating water flow °C 20 to 58 ± 2
Brine (heat source) °C -5 to +25
Antifreeze Monoethylene glycol
Minimum brine concentration (-13 °C freezing temperature) 25% 25% 25% 25%
4 Performance data / flow rate
1
1. This data indicates the size and capacity of the system according to EN 14511 (5K at B0/W35). For an analysis of the economic and energy efficiency of the system, both the
bivalence point and the regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, start-
up and operation can be found in the respective sections of the installation and operating instructions. The specified values, e.g. B10 / W55, have the following meaning: Heat
source temperature 10 °C and heating water flow temperature 55 °C.
4.1 Heating water flow rate / internal pressure differential
maximum m³/h / Pa 7.8 / 6400 12.5 / 8500 16.3 / 14200 21.0 / 7100
minimum m³/h / Pa 3.6 / 1400 5.6 / 1700 7.6 / 3100 9.6 / 1500
4.2 Heat output / COP
2
2. At maximum heating water flow rate
EN 14511 EN 14511 EN 14511 EN 14511
at B-5 / W45 kW / ---
3
3. Operation with 2 compressors
38.0 / 2.8 59.7 / 2.8 77.9 / 3.0 99.0 / 2.7
kW / ---
4
4. Operation with 1 compressor
17.1 / 2.6 30.6 / 2.7 41.4 / 2.7 43.9 / 2.6
at B0 / W55 kW / ---
3
41.3 / 2.5 61.9 / 2.4 85.1 / 2.7 102.6 / 2.4
kW / ---
4
19.4 / 2.4 31.9 / 2.4 36.1 / 2.3 45.9 / 2.4
at B0 / W45 kW / ---
3
43.4 / 3.3 67.3 / 3.1 88.7 / 3.3 112.9 / 3.1
kW / ---
4
21.6 / 3.2 34.4 / 3.1 42.0 / 3.2 53.6 / 3.1
at B0 / W35 kW / ---
3
45.8 / 4.3 72.7 / 4.2 92.3 / 4.4 122.0 / 4.1
kW / ---
4
23.2 / 4.3 36.1 / 4.1 46.3 / 4.3 60.8 / 4.1
4.3 Sound power level according to EN 12102 dB(A) 57 63 65 67
4.4 Sound pressure level at a distance of 1m
5
dB(A)
5. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C. The specified sound pressure level
represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
49 53 54 55
4.5 Brine flow with an internal pressure differential (heat source) of m³/h / Pa 11.1 / 13400 19.6 / 16700 21.5 / 19500 34.0 / 26200
4.6 Refrigerant / total filling weight type / kg R404A / 8.6 R404A / 14.1 R404A / 20.5 R404A / 27.0
4.7 Lubricant / total filling quantity type / litres
Polyolester
(POE) / 6.5
Polyolester
(POE) / 6.5
Polyolester
(POE) / 13.2
Polyolester
(POE) / 16.0
5 Dimensions, connections and weight
5.1 Device dimensions without connections
6
H x W x L mm
6. Note that additional space is required for pipe connections, operation and maintenance.
1890 x 1350 x 775
5.2 Device connections for heating system Inches
G 1 1/2'' internal/
external
G 2'' internal/
external
G 2'' internal/
external
G 2 1/2'' internal/
external
5.3 Device connections for heat source Inches
G 2 1/2'' internal/
external
G 2 1/2'' internal/
external
G 3'' internal/
external
G 3'' internal/
external
5.4 Weight of the transportable unit(s) incl. packaging kg 486 571 652 860
6 Electrical connection
6.1 Supply voltage; fuse protection
3~/PE 400 V
(50 Hz) / C 50A
3~/PE 400 V
(50 Hz) / C +63A
3~/PE 400 V
(50 Hz) / C 80A
3~/PE 400 V
(50 Hz) / C 80A
6.2 Control voltage / fuse protection 1~/N/PE 230 V (50 Hz) / C 13A
6.3 Nominal power consumption B0 W35
3
/ max. power consumption
1
kW
10.65 / 17.0 17.31 / 30.0 20.98 / 36.0 29.76 / 45.0
6.4 Starting current with soft starter A 63 105 120 115
6.5 Nominal current B0 W35 / cos
3
A / ---
19.21 / 0.8 31.23 / 0.8 37.85 / 0.8 53.69 / 0.8
6.6 Max. power consumption of compressor protection
(per compressor) W
65 65 75 130
7 Complies with the European safety regulations
7
7. See CE declaration of conformity
777
8 Additional model features
8.1 Water in device is protected against freezing
8
8. The heat circulating pump and the heat pump manager must always be ready for operation.
YesYesYesYes
8.2 Max. operating overpressure (heat source/heat sink) bar 3.0 3.0 3.0 3.0