Alternate installations for close clearances
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
Over-The-Top installation (also available with one offset elbow)
Periscope installation
NOTE: The following kits for close clearance alternate
installations are available for purchase.
Venting Kits
For more information, visit us at www.whirlpool.com/accessories
or contact the dealer from whom you purchased your dryer or an
authorised service company.
Part Number Descriptions
8171587RP 0–5" Metal vent periscope
4396037RP 0"–18" Metal vent periscope
4396011RP 18"–29" Metal vent periscope
4396014 29"–50" Metal vent periscope
4392892 In-Wall metal DuraVent Periscope
4396028 Sure Connect venting kit
(over-the-top installation)
4396009RP 5' Universal connect vent, exible dryer venting
4396010RP 6' SecureConnect vent, exible dryer venting
4396013RB Dryer vent installer’s kit
4396033RP 5' exible dryer venting with clamps
4396727RP 8' exible dryer venting with clamps
4396004 Dryer offset elbow
4396005 Wall offset elbow
4396006RW DuraSafe close elbow
4396007RW Through-the-wall vent cap
4396008RP 4" steel dryer venting clamps—2 pack
8212662 Flush-mounting louvered vent hood 4"
Special provisions for mobile home installations:
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path:
n Select route that will provide straightest and most direct path
outdoors.
n Plan installation to use fewest number of elbows and turns.
n When using elbows or making turns, allow as much room
as possible.
n Bend vent gradually to avoid kinking.
n Use as few 90° turns as possible.
Determine vent length and elbows needed for best
drying performance:
n Use following “Vent System Chart” to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied
in “Vent System Chart.” Exhaust systems longer than those
specied will:
n Shorten life of dryer.
n Reduce performance, resulting in longer drying times and
increased energy usage.
The “Vent System Chart” provides venting requirements that
will help achieve best drying performance.
Vent System Chart
Number of
90° turns
or elbows
Type
of vent
Box/
louvered
hoods
Angled
hoods
0 Rigid metal 20 m (64 ft.) 17.7 m (58 ft.)
1 Rigid metal 16.5 m (54 ft.) 14.6 m (48 ft.)
2 Rigid metal 13.4 m (44 ft.) 11.6 m (38 ft.)
3 Rigid metal 10.7 m (35 ft.) 8.8 m (29 ft.)
4 Rigid metal 8.2 m (27 ft.) 6.4 m (21 ft.)