INSTALLATION
ENGLISH
Flexible Connector Hookup
1
/
2
"
Adapter
Pressure regulator
Flex connector
(6 ft. max.)
Adapter
Gas shut-off
valve
1
/
2
" or
3
/
4
" Gas
pipe
Gas Flow into Range
Installer: Inform the consumer of the location of the gas
shutoff valve
.
Pressure Regulator Position
Pressure Regulator
Connecting Electricity
Electrical Requirements
This appliance must be installed and grounded on a
branch circuit by a qualified technician in accordance
with the National Electrical code ANSI/NFPA NO. 70 -
latest edition.
All wiring should conform to Local and NEC codes.
This range requires a single-phase, 3 wire, A.C
120/208 V or 120/240 V 60 Hz electrical system. Use
only a 3-conductor or a 4-conductor UL- listed range
cord with closed-loop terminals, open-end spade
lugs with upturned ends or similar termination. Do not
install the power cord without a strain relief.
A range cord rated at 40 amps with 120/208 or
120/240 minimum volt range is required. If a 50 amp
range cord is used, it should be marked for use with
1
3
/
8
" diameter connection openings. This appliance
may be connected by means of a conduit or power
cord. If a conduit is being used, go to page 23 for
3 wire conduit connections or 4 wire conduit
connections.
WARNING
Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack
in the line so that the range can be moved if
servicing is ever necessary.
The power supply cord and plug should
not be modified. If it will not fit the outlet,
have a proper outlet Installed by a qualified
electrician.
Using an extension cord to connect the
power is prohibited. Connect the power cord
and plug directly.
Electrical ground is required on this appliance.
Make sure that the power cord is not pinched
by the range or heavy objects. Failure to do so
can result in serious burns or electrical shock.
Do not use a damaged power plug, power
cord, or loose power outlet.
Do not put a fuse in a neutral or ground circuit.
Do not connect the ground wire to plastic
plumbing lines, gas lines, or hot water pipes.
Specified power-supply-cord kit rating
Range rating, watts
Specified
rating of
power
supply-
cord kit,
amperes
Diameter (inches)
of Range
connection
Opening
120/240
volts
3-wire
120/208
volts
3-wire
Power
cord
Conduit
8,750 -
16,500
16,501 -
22,500
7,801 -
12,500
12,501 -
18,500
40 or 50A
50
1
3
/
8
"
1
3
/
4
"
1
1
/
8
"
1
3
/
8
"
3, 4 - Wire electrical wall Receptacle
4 Wire receptacle (14-50R)
3 Wire receptacle (10-50R)
Connecting the Power Cord
The rear access cover must be removed. Loosen the
two screws with a screwdriver. The terminal block will
then be accessible.
Access cover