GB 29
INSTALLATION
Electrical connection
Common connections:
2 phase and 1 zero connection (2 1N, 400 V~/ 50 Hz):
The voltage between the phases and the neutral is 230 V~. The
voltage between the two phases is 400 V~. Fit a connecting
bridge between connecting points 4-5. The groups must have
fuses of at least 16 A (2x). The core diameter of the connecting
cable must be at least 2.5 mm
2
.
2 phase and 2 neutral connection (2 2N, 230 V~ / 50 Hz):
The voltage between the phases and the neutral is 230 V~.
The group must have fuses of at least 16 A (2x). The core
diameter of the connecting cable must be at least 2.5 mm
2
.
• WARNING: You may use two live and only one neutral conductor. In
this case, make sure a jumper connector is installed over connection
points 4 and 5.