2. When the indoor humidity < set humidity - 5% RH, the compressor is turned off.
3. Set the humidity - 5% RH < indoor humidity < set humidity + 5% RH to keep the original
compressor working.
4. The compressor stops the fan if it has not been operated for three minutes after the humidity
has dropped.
5. When the machine beeps three times and the water full indicator light is on, the machine stops
working. The water in the water tank needs to be drained and the water tank is reinstalled. If the
water full indicator light is still on, check whether the water tank is in place. The operation is
started until the water full indicator is off.
6. Defrost
A) After the machine starts to run for 30 minutes, the copper head coil sensor starts to detect the
tube temperature. When the tube temperature is -1 °C (there is 3 seconds of detection time),
the compressor stops and the fan runs, and the defrosting operation starts. The lights are shining.
B) When the temperature sensor detects that the coil temperature on the evaporator is greater
than or equal to 5 degrees and the detection is greater than or equal to 5 degrees for 3 minutes,