58 Outside Unit
Electrical Wiring
Dip switch setting
1. Location of setting switch
2. Dip switch setting
1) Set the dip switch and turn on the power of the outside unit to check whether the set value is correctly
entered in the 7 segment.
2) This function is shown for only 2 seconds after the power is connected.
n Check outside unit setting
• The number on the 7 segment is displayed in order after the power is connected.
• This number represents the setting condition.
n Mode code
If the applicable dip switch is not set correctly,
the product may not operate properly.
SW01B
SW02B
7 segment
SW01B
1234567
ON
SW02B
1234567
ON
Order Number Item
1 - Model code
2 - Total capacity(HP)
3 2 Heat pump model
4 25 Normal mode display (If the dip switch is set incorrectly, it is not displayed.)
5
133 Model type (220V)
131 Model type (460V)
220V 460V
Refrigerant
Model Code Capacity (HP) Model Code Capacity (HP)
155 8 138 10
R410A
156 16 139 20
156, 155 24 139, 138 30
156, 156 32 139, 139 40
156, 156, 155 40 139, 139, 138 50
156, 156, 156 48 139, 139, 139 60