Installation Manual 41
Refrigerant piping system
Branch pipe Fitting
Y branch
A
B
To Outside Unit
To Branch Piping or Indoor Unit
A
B
Facing
upwards
Facing
downwards
Within 3 Within 3
Viewed from point A
in direction of arrow
Horizontal
plane
Within +/- 10
A
Insulator
(included with kit)
Liquid and gas
pipe joints
Insulator for
field piping
Tape
(field supply)
Header
To outside unit
To indoor unit
A
B
A
B
C
• Ensure that the branch pipes are attached horizontally or vertically (see the diagram below.)
• There is no limitation on the joint mounting configuration.
If the diameter of the refrigerant piping selected by the procedures described is different from the size
of the joint, the connecting section should be cut with a pipe cutter.
• Branch pipe should be insulated with the insulator in each kit.
When the number of pipes to be connected is
smaller than the number of header branches,
install a cap to the unconnected branches.
• The indoor unit having larger capacity must be
installed closer to than smaller one.
• If the diameter of the refrigerant piping selected
by the procedures described is different from
the size of the joint,
the connecting section
should be cut with a pipe cutter.
Pipe cutter