Installation Manual 101
ENGLISH
New Function
1. Cool/ Heat selector
Cool/ Heat Selector has provided two different functions.
- Cooling/ heating/ Fan lock mode
- Cooling/ heating/ All OFF mode
[Installation]
1. Check the contents of Cool/ Heat Selector
2. Connect Outdoor Main PCB and Cool/ Heat Selector.
-. Connect terminals on the back side of Cool/Heat Selector to terminal of Outdoor as show
¨
GNDGND
¨≠
GND
< Outdoor Main PCB >
- Insert wire method -
shows field wiring
connected wiring
Push arrow direction.
Insert wire to connector.
Push Button
<Outdoor Dry Contact Back Side >
¨
¨
GNDGNDGND
1
2
3
4
1
2
3
4
Communication line length can be maximum 300m, use communication line as thick as 1.25mm
2
.
<Front Case><Outdoor Dry Contact Main Body>
[setting]
1. Set DIP S/W according to DIP S/W
setting table.(5,6,11,12)
2. Push Black button on SVC PCB
3. Select number as below at 7-segment
“0” : Cooling/ Heating / Fan lock mode
“1” : Cooling/ Heating/ All OFF Mode
4. After Selecting, DIP S/W OFF(11,12 )
SW01B
SW02B
Setting Button
7-Segment