8.914-458.0-G • Water Maze CLB-603
11
WATER TREATMENT SYSTEM
OPERATOR’S MANUAL
set to inject during system non-use hours.
Pulling a pin on this timer will cause the Microbe
and Nutrient pump to operate automatically
when their hand switches are on.
11. Water Panel Connections:
a. Connect a garden hose from the city water sup-
ply to the "Fresh Water Inlet" connection on the
water panel. Refer to Water Panel Installation
Drawing. Make sure hand valve V5 is open.
b. Connect a garden hose from "Outlet to Pres-
sure Washer" on water panel to your pressure
washer. Make sure hand valve V7 is open.
Installation Checklist
Is all piping connected as shown on the Instal-
lation and Piping Diagrams?
Is electrical wiring connected as shown on the
Electrical Connection Diagram?
Are air lines connected as shown on the Air
Connection Diagram?
Is the voltage correct?
Is the fresh water make-up hose connected?
Is the outlet to pressure washer hose con-
nected?
Is the rainwater overfl ow connected?
a. Mix microbes and nutrient in separate fi ve gal-
lon containers supplied.
b. Install tubing to pumps and connect to injection
probes located on side of CLB-603 tank. Refer
to attached information for installation and con-
nections.
10. Set Timers
There are four timers in your control panel enclo-
sure that need to be set. Open control panel door
to set timers. Timers are 24 hour and each pin
represents half an hour. NOTE: Always remove
electrical power from control panel prior to open-
ing the door. Rotate each timer until the hour at
the center of the dial meets the actual time of day
(a.m. or p.m.). After each timer is set for the time
of day, proceed to instructions below to set timers
to actuate equipment.
a. Infeed Pump Timer: Pull 1 Pin Separated
by 2 Pins (repeat 4 times)
The infeed pump timer provides for water cir-
culation during system non-use hours to aid in
circulation of dissolved air and biodigestion by
microbes. Circulation of water must be paused
for tank dwell time. Pulling one pin separated
by two pins (and repeated 4 times) will allow
for 30 minutes of water circulation separated
by one hour of dwell time. Pulling a pin on this
timer will cause the infeed pump to operate
automatically when the hand switch is on. The
circulation pump should be set to operate
during system non-use hours.
b. Ozone Timer: Pull 4 Pins.
The ozone timer controls the amount of time
that the ozone pump and ozone generator op-
erate. Pulling a pin on this timer will cause the
ozone pump and ozone generator to operate
automatically when their hand switches are
on. Ozone water is circulated to the recycle
holding tank to provide disinfected water. The
ozone timer should be set to operate during
system non-use hours.
c. Purge Timer: Pull 1 Pin
The purge timer controls the amount of time
that the tank purge valve operates. The purge
valve provides for sludge removal from the
bottom of the cone tank. Pulling a pin will al-
low for automatic energizing of the ten second
timer which causes the purge drain valve to
open. Set timer to coordinate with daily
maintenance schedule.
d. Microbe / Nutrient Timer: Pull 3 Pins
This timer determines the amount of microbes
and nutrients that are added to the CLB-603
tank. The microbe / nutrient timer should be
INSTALLATION INSTRUCTIONS
Loading ...
Loading ...
Loading ...