Installation requirements
English16
Installation requirements
Ducting requirements
Weather hood type
Recommended
Use only for short-run
installation
4” (10.2 cm) 2.5” (6.4 cm)
No. of 90° elbows Rigid Rigid
0 120 ft. (36.6 m) 114 ft. (34.7 m)
1 110 ft. (33.5 m) 104 ft. (31.7 m)
2 100 ft. (30.5 m) 94 ft. (28.7 m)
3 90 ft. (27.4 m) 84 ft. (25.6 m)
NOTE
The above table only states the allowable vent system length with up to 3 elbows. If
you need more than 3 elbows for your vent system, reduce the total allowable vent
system length by 10 ft. (3.05 m) per each elbow.
The total length of exible metal duct must not exceed 7’ 10½” (2.4 m).
Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer’s vent system with an existing exhaust system:
Make sure the exhaust system meets all applicable local, state, and national regulations.
Verify you are not using exible plastic duct.
Make sure to check for and remove all lint buildup from inside the existing ducts.
Conrm the duct is not kinked or crushed.
Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column
or be less than 0. Note that these values are measured with the dryer running with a
manometer presented to the exhaust duct that connects to the dryer. The dryer tumbler
must be empty and lint lter clean.