THE INDOOR UNIT INSTALLATION
17
ENGLISH
Position of console Bolt
- A place where the unit will be leveled and
that can support the weight of the unit.
- A place where the unit can withstand its
vibration.
- A place where service can be easily
performed.
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4
(Local
supply)
X 4
- Insert the set anchor and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the set
anchor firmly.
- Secure the installation plates onto the
suspension bolts (adjust level roughly) using
nuts, washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
• Local supply
Set anchor
Plate washer - M10
Spring washer - M10
Nut - W3/8 or M10
Suspension bolt - W3/8 or M10
CAUTION
• Tighten the nut and bolt top revent unit
falling.
!
CAUTION
1. Install declination of the indoor unit is
very important for the drain of the duct
type airconditioner.
2. Minimum thickness of the insulation
for the connecting pipe shall be 10
mm.
!
1~3 mm
Drainage hole
Drainage hole
Safety drain hole Main drain hole