EXTERNAL STATIC PRESSURE
ENGLISH
EXTERNAL STATIC PRESSURE
* Only for ceiling concealed duct type
Capacity
(kBtu/h)
Step CMM
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
24
LOW 14.5 76 77 85 89 97 106 114 121 124 127 132
MID 16.5 85 87 90 94 103 111 118 125 128 131 136
HIGH 18 90 92 95 99 108 115 122 129 132 135 138
Capacity
(kBtu/h)
Step CMM
Static Pressure[mmAq(Pa)]
4(39) 5(49) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
36
LOW 24 88 91 95 100 101 108 113 115 118 121 128
MID 28 93 97 101 105 108 115 118 120 124 127 134
HIGH 32 101 105 109 112 115 119 123 126 128 133 137
NOTE
!
1. Be sure to set the value refering table 2. Unexpected set value will cause mal-function.
2. Table 2 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
* If it is zero static pressure, please set value below Maximum value.
Capacity (kBtu/h) Maximum value
24 115
36 120
Capacity (kBtu/h) Factory set (E.S.P.) mmAq(Pa)
24
6(59)
36