INSTALLATION INSTRUCTIONS
Connecting dryer using 3-wire connection
If required, by local code, install external ground (not provided) to grounded metal,
coldwater pipe, or other established ground determined by a qualified electrician.
L1
N
L2
Cover
Ground strap
3/4” Strain relief
and bracket
3 #10 AWG minimum copper conductors or 120/240V 30A power supply cord kit marked for use with
dryers and provided with closed loop or spade terminals with upturned ends (not supplied)
Three-wire connection
z
Not for use in Canada.
z
DO NOT use for Mobile Home Installations.
z
NOT for use on new construction.
z
NOT for use on recreational vehicles.
z
NOT for use in areas where local codes prohibit grounding through the
neutralconduction.
1 Turn off the circuit breaker(s) (30 amp) or remove the dryer’s circuit fuse at the
electrical box.
2 Be sure the dryer cord is unplugged from the wall receptacle.
3 Remove the power cord cover located at the upper back.
4 Install 3/4 in. UL-recognized strain relief to power cord entry hole.
Bringpowercordthrough strain relief and bracket.
5 Connect power cord as follows:
z
Connect the 2 hot lines to the outer screws of the terminal block (marked L1 and L2).
z
Connect the neutral (white) line to the center of the terminal block (marked N).
6 Be sure ground strap is connected to green ground screw on cabinet rear.
Tightenallterminal block screws (3) securely.
7 Properly secure power cord to strain relief and bracket.
8
Reinstall the cover.
IMPORTANT!
Never leave the cover off of the terminal block.