LG Electronics ARWB072DAS4

User Manual - Page 19

For ARWB072DAS4.

PDF File Manual, 45 pages, Download pdf file

Loading ...
Loading ...
Loading ...
19
ENGLISH
WARNING
• In case of pipe diameter B connected after first branch is bigger than
the main pipe diameter A, B should be of the same size with A.
Ex) In case indoor unit combination ratio 120% is connected to
16Ton[20HP(58kW)] outside unit .
1) Outside unit main pipe diameter A : Ø28.58(1-1/8”)(gas pipe),
Ø12.7(1/2”)(liquid pipe)
2) Pipe diameter B after first branch according to 120% indoor
unit ombination(69.6kW) : Ø28.58 (1-1/8”)(gas pipe),
Ø15.88(5/8”) (liquid pipe)
Therefore, pipe diameter B connected after first branch would be
Ø28.58(1-1/8”) (gas pipe) / Ø12.7(1/2”)(liquid pipe) which is same with
main pipe diameter.
!
Outside unit Connection
Indoor Unit Connection
Indoor unit connecting pipe from branch (a~f)
Indoor Unit capacity
[kW(Btu/h)]
Liquid pipe
[mm(inch)]
Gas pipe
[mm(inch)]
5.6(19,100)
Ø6.35(1/4) Ø12.7(1/2)
< 16.0(54,600) Ø9.52(3/8) Ø15.88(5/8)
< 22.4(76,400) Ø9.52(3/8) Ø19.05(3/4)
< 28.0(95,900) Ø9.52(3/8) Ø22.2(7/8)
CAUTION
• Bending radius should be
at least twice the diameter
of the pipe.
• Bend pipe after
500mm(1.64ft) or more
from branch(or header).
Do not bend U type.
It may cause Performance
unsatisfactory or noise.
!
500mm(1.64ft)
or more
500mm(1.64ft)
or more
Pipe Connection Method/Precautions for
Series connections between Outside units
- Separate Y branch joints are needed for series connections between
outside unit s.
- Please refer to the below connection examples to install pipe connec-
tions between outside unit s.
- If the distance between the outside unit s becomes more than
2m(6.6ft), apply Oil Traps between the gas pipes.
- If the outside unit is located lower than the main pipe, apply Oil Trap.
Pipe connection between outside
unit s (General Case)
The maximum pipe
length after the first
branching between the
outside unit is 10m(33ft)
or less
Pipes between outside unit s
are 2m(6.6ft) or less
2m(6.6ft) or less
Pipes between outside unit
s are 2m(6.6ft) or longer
Oil Trap
Oil Trap Oil Trap
2m(6.6ft) or less
2m(6.6ft) or less
2m(6.6ft) or less
0.2m(0.66ft) or more
2m(6.6ft) or longer
2m(6.6ft) or longer
2m(6.6ft) or longer
Oil trap application method between outside units
- Because of the possibility of oil being accumulated in the outside unit
that has stopped, when there is a height difference between outside
unit pipes or if the pipe distance between the outside units is over
2m(6.6ft), you must always apply an oil trap. (But, the oil trap be-
tween outside units is limited to 1 time and is only applied to the gas
pipe.)
- If the pipe distance between the outside units is 2m(6.6ft)
or below, and if the location of the main pipe is lower than that of the
outside unit and if the location of the main pipe is lower than that of
the outside unit, the oil trap does not have to be applied.
- If the location of the main pipe is higher than the location of the out-
side unit, be careful since the oil can be accumulated in the stopped
outside unit.
- If there is high/low difference between the outside unit pipes, oil can
be accumulated to the outside unit on the lower location until the unit
stops.
- The pipes between the outside unit s must maintain horizontal level-
ness or give an inclination to prevent a back flow toward the slave
outside unit . Otherwise, the unit may not operate properly.
Examples of Wrong Pipe Connections
If the main pipe is
higher than the
outside unit, oil is
accumulated in the
outside unit.
If there are differences in the height
between the outside unit, oil is
accumulated in the lower outside unit.
Oil Trap
Toward indoor unit
Toward indoor unit
Pipe inclination
(2 or more)
Toward indoor unit
Toward indoor unit
Toward indoor unit
Toward indoor unit
(Example 1)
(Example 2)
(Example 3)
Loading ...
Loading ...
Loading ...