Installation Manual 73
Test Run
How to Cope with Test Run Abnormality
The phenomena from main component failure
Compressor
Outdoor
fan
Outdoor
EEV
Not operating
Stop during running
High pressure error
at cooling
Heating failure, fre-
quent defrosting
No operating sound
at applying power
Heating failure,
Frozen outdoor heat
exchanger part
Low pressure error
or discharge temper-
ature error
Motor insulation broken
Motor insulation failure
Motor failure,
Bad ventilation around
outdoor heat exchanger
Bad connector contact
Coil failure
EEV clogged
EEV clogged
Check resistance between terminals and
chassis
Check resistance between terminals and
chassis
Check the outdoor fan operation after being
turned the outdoor units off for some time.
Remove obstacles around the outdoor units
Check connector
Check resistance between terminals
Service necessary
Service necessary
Component Phenomenon Cause Check method and Trouble shooting
When system fault occurs, the error code is displayed at indoor unit display or remote control display, the trou-
ble shooting guide is in the service manual