Loading ...
Loading ...
Loading ...
26 Outdoor Unit
Refrigerant piping installation
Select an HR unit according to the number of the indoor units to be installed. HR units are classified into 3 types
by the number of connectable indoor units.
Ex) Installation of 6 indoor units
Consists of HR unit for 4 rooms and HR unit for 2 rooms.
Type of HR Unit
PRHR030A(3 rooms)PRHR020A(2 rooms) PRHR040A(4 rooms)
1
2
3
1
2
1
3
2
4
WARNING
• 1 port of HR unit allows up to 14.1kW based on cooling capacity of the indoor unit (up to 14.1kW
(48MBh) for max installation).
• The maximum total capacity of the indoor units connected to one PRHR040 HR unit is 47kW
(160MBh). In case of installation of four indoor units of 14.1kW (48MBh), use two PRHR020's rather
than one PRHR040.
Gas pipe Ø15.88
Liquid pipe Ø9.52
BraGing Gype
1
2
3
4
RemoGe caps on
Ghe braGing part.
Liquid pipe
Low pressure gas pipe
High pressure gas pipe
(Unit: mm)
HR unit PRHR020A PRHR030A PRHR040A
Low pressure gas pipe Ø22.2(7/8) Ø28.58(1-1/8) Ø28.58(1-1/8)
High pressure gas pipe Ø19.05(3/4) Ø22.2(7/8) Ø22.2(7/8)
Liquid pipe Ø9.52(3/8) Ø12.7(1/2)
Ø12.7(1/2)(Before 2011.4.1 Product)
Ø15.88(5/8)(After 2011.4.1 Product)
Loading ...
Loading ...
Loading ...