Renogy MDN-OS-MNEDC-QUAD-US MidNite MNEDC-Quad Enclosure For 1-4 Solar Panel Mount Breakers

User Manual - Page 3

For MDN-OS-MNEDC-QUAD-US.

PDF File Manual, 4 pages, Read Online | Download pdf file

MDN-OS-MNEDC-QUAD-US photo
Loading ...
Loading ...
E-Panel Instructions (continued)
3 | P a g e 1 0 - 0 7 0 - 1 R E V : A
Torque Ground Box Lug
10AWG 20 in-lbs (2.3Nm)
8AWG 25 in-lbs (2.8Nm)
6AWG 35 in-lbs (4.0Nm)
4AWG 45 in-lbs (5.1Nm)
2AWG 1/0 50 in-lbs (5.6Nm)
Torque Circuit Breaker to 20 in-lbs (2.3Nm)
Re-torque after 1 hour
Big Baby
The Baby Box was hugely successful in filling an industry need, but was just a little small so the Big Baby was developed to
meet the need for a medium sized breaker box.
Big Baby Enclosure
Installation:
Select a safe dry indoor or sheltered location and secure to the wall with appropriate screws or wall anchors.
The Big baby is a general purpose enclosure and may be used with up to four 13mm wide dinrail AC or DC breakers.
Midnite Solar breakers available at your local dealer are highly recommended such as MNEPVXX where XX is the breaker
rating. For example MNEPV10 is a 10 amp breaker. Other Midnite breakers and GFP’s (Ground Fault Protectors) are available
from your dealer. Use breakers rated for a max of 300 VDC or 277 VAC.
Wiring:
It is the installer’s responsibility to ensure compliance the National Electrical
Code, ANSI/NFPA 70 and all applicable local codes. A box lug is provided
for grounding of the enclosure. The Big Baby is designed for up to 6AWG
wire. Use of larger wire will reduce the required bending room allowance.
Knockouts are provided at the top and bottom of the Big Baby. You will
need a hammer, screwdriver and needle nose pliers to remove knockouts.
DIN Rail
Ground Lug
Breaker Knockouts