Installation Set-up and System Start-up
Liebert
®
SRC
User Manual 88
5. Press then to select the next Step.
6. Press to select the Value, then use to select the setting.
7. Repeat Step s5 to 6 until the strength is set for each wind level.
8. Press .
The setting is saved.
Press to
exit installer setting mode.
7.5 Setting the Thermistor
Refer to Table 7-1 for the specific function-setting values.
1. On the thermostat, press for at least 3 seconds.
The function code blinks in the lower-middle of the display.
2. P ress repeated ly to select the function code.
3. Press ,
to select Value, then use to select the setting. Refer to Table 7-2 for descriptions of
the thermistor settings.
4. Press .
The setting is saved.
5. Press to exit installer setting mode.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
NOTE
A press less than 3 seconds enters “user” settings mode.
Table 7-2 Thermistor setting options
Value Function
01 Thermostat Operates based on temperature sensor in thermostat.
02 Indoor Unit Operates based on temperature sensor in indoor unit.
032TH
Cooling
Operates based on higher temperature comparing the
reading from thermostat temp. sensor and indoor-unit
temp sensor.
Heating
Operates based on lower temperature comparing
the
reading from thermostat temp. sensor and indoor-unit
temp sensor.
The 2TH functions differently depending on product model.
If the indoor temperature is below 10°F, the value for the temperature sensor of the thermostat is
displayed regardless of the thermistor setting.
NOTE
If there is no button input for 25 seconds, set-up mode is automatically exited.
If you exit without pressing , your settings are not saved.
MFL67502030 17. 7. 13. 오오 3:05 Page 98