Power Connection Kits For
Premium Series (5200)
The Zoneline 5200 series units are connected to the
building power supply by a unique power connection kit. By
utilizing a separate universal power connection (UPC) kit,
each unit is capable of providing various outputs of electric
resistance heat to more closely meet the heating
requirements of the particular room, thereby increasing the
installation flexibility of the particular chassis. This power
connection kit is the only means of supplying power to the
Zoneline chassis and the appropriate kit is determined by
the voltage, the means of electrical connecton - either line
cord connected or permanent connected - and the desired
resistance heat output that may be supported by the branch
circuit.
230/208 Volt Installations
Connections to 208 or 230 volt circuits may be made with a
line cord power connection kit.
Line Cord Kits consist of a self-aligning 9-pin molded
connector that plugs into a mating connector on the
Zoneline chassis and insulated line cord with an electrical
plug on the end. The configuration of the electrical plug
conforms to NEC standards for the circuit amperage and the
postion of the wires in the 9-pin connector determines the
heater wattage and current requirements when it is plugged
into the Zoneline chassis. Permanent
Connection is accomplished by ordering the correct
ampacity electrical sub-base to match the Power Cord being
used. See page 21 Sub-Base for description.
There may be special requirements by some sites that rigid
or flexible conduit be used. (Such as the wall case must be
installed flush to finished floor and there is no room for a
sub-base.) In these installations the RAK4002 junction box
will be needed and the Power Cord/Cord Set will be cut and
connected to building wiring inside the RAK4002 junction
box. Conduit will be attached to the RAK4002 and to the
site supplied building/room junction box where the
building wiring enters the room. Wiring will be totally
enclosed by conduit and junction boxes.
Maximum Cord Extension
Premium
Typical Line Cord
Power Connection Kit
Line Cord Heater Circuit Protective
Kit Voltage KW Ampacity Device
RAK3152 230/208 2.55/2.09 15 Amp 15 Amp
Time Delay
Fuse or Breaker
RAK3202 230/208 3.45/2.82 20 Amp 20 Amp
Time Delay
Fuse or Breaker
RAK3302 230/208 5.00/4.09 30 Amp 30 Amp
Time Delay
Fuse or Breaker
Receptacle
Type Mfg Part No Configuration
15 AMP GE GE4069
Tandem Hubbell 5661
NEMA6-15R P&S 5661
20 AMP GE GE4182
Perpen- Hubbell 5461
dicular P&S 5871
NEMA6-20R
30 AMP GE GE4139-3
Large Hubbell 9330
Tandem P&S 5930
NEMA6-30R