The Diagnostic Maintenance & Status Report provides detailed information on PTAC control operation and operational status includ-
ing present modes, failures, airflow restriction warnings, operating temperatures, and past failures. The lower right hand dot on the
center display flashes in this mode. In some cases the green LED located in the lower left hand corner of the touchpad below the OFF
key will also be lit. This Green LED “Status Light“ only illuminates if there is an status code that has been activated and should be
reviewed. In most cases, this light indicates that the indoor room filter is dirty should be cleaned or replaced. NOTE: Dirty filters
cause the unit to consume more energy than normally needed to condition a room. Once the filter has been cleaned or replaced, the
LED should go out. If the LED is still illuminated after the filter has been cleaned, activate the Diagnostic and Status mode to view
any active codes. The unit may need additional cleaning or maintenance of the evaporator or condenser coils. Please perform this
step before calling a servicer. A servicer should be called only if cleaning the filter or coils does not clear the status code or
the code indicates that servicer should be called.
DIAGNOSTIC STATUS REPORT MODE.
To enter Diagnostic Status Report mode, press and hold the up and down arrows and, while holding, quickly press the
COOL key
twice.
ACTIVE FAILURES.
If there are no active failures or lockouts, the display will show a double dash, “- -”. If there is a code listed, see the unit “Diag-
nostic Codes” chart for a list of definitions.
OPERATING TEMPERATURES.
If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key.
If already in Diagnostic Status Report mode, press the Fan Speed key. The display will show the temperature of the de-
sired set point, SP; the temperature at the wireless thermostat, rL; the indoor ambient temperature behind the filter, IA; the indoor
coil temperature, IC; the indoor discharge air temperature, Id; the outdoor coil temperature, OC; the outdoor ambient tempera-
ture, OA; and the spare probe temperature, IH. If any of the probes are not populated the display will show the corresponding
failure code.
PAST FAILURE LOG
If not in Diagnostic Status Report Mode, enter as instructed above and press the Fan Speed key twice.
If already in Diagnostic Status Report mode, press the Fan Speed
key. While the display is showing operating tempera-
tures, the last 10 failure codes active or past can be requested by pressing the Fan Speed key again. The codes are dis-
played last entry first followed subsequently by each preceding code.
Note that modes F1 and Fd are also displayed in the normal control operation (see “Diagnostic Codes” chart).
To exit Diagnostic Status Report mode, press the OFF key.
Diagnostic Maintenance & Status Report