MAXIMUM CONNECTED LOAD
The maximum connected load of a Zoneline unit occurs when the unit is in resistance heating operation. The maximum
amperage shown in the tables below is the combined total of the resistance heater and the indoor fan motor.
230/208-Volt Line-Cord Connected Units
Power Connector Kit
RAK3153A
RAK4157
RAK204D15P
RAK3203A
RAK4207
RAK204D20P
RAK3303A
RAK4307
RAK204D30P
MODEL
NUMBER
230 V 208 V 230 V 208 V 230 V 208 V
AZ41E07DA* 11.0 11.6 15.1 16.0 N/A N/A
AZ41E09DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ41E12DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ41E15DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ61H07DA* 11.0 11.6 15.1 16.0 N/A N/A
AZ61H09DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ61H12DA* 11.0 11.6 15.1 16.0 21.2 22.4
AZ61H15DA* 11.0 11.6 15.1 16.0 21.2 22.4
*All versions
Electric Heat Amps include electric heater and fan motor current draw.
265-Volt Units
Sub-Base/Power Connector Kit
RAK204E15
RAK5172
RAK5157
RAK204E20
RAK5202
RAK5207
RAK204E30
RAK5302
RAK5307
MODEL
NUMBER
265 V 265 V 265 V
AZ41E07EA 9.6 13.3 N/A
AZ41E09EA* 9.6 13.3 18.6
AZ41E12EA* 9.6 13.3 18.6
AZ41E15EA* 9.6 13.3 18.6
AZ61H07EA* 9.6 13.3 N/A
AZ61H09EA* 9.6 13.3 18.6
AZ61H12EA* 9.6 13.3 18.6
AZ61H15EA* 9.6 13.3 18.6
*All versions
Electric Heat Amps include electric heater and fan motor current draw.
LATENT SYSTEM CAPACITY
The total capacity of an air conditioner is made up of the
sensible capacity, the output of the unit used to remove
heat from the air in the area being conditioned, and the
latent capacity, the output of the unit used to dehumidify
the air in the area being conditioned. For humid climates
and applications, the sensible/latent capacity split of the
unit should be considered. The sensible capacity listed in
the specification charts on pages 54 and 55 is at a standard
rating condition of 95°F dry bulb/75°F wet bulb outdoors; 80°F
dry bulb/67°F wet bulb indoors. The latent system capacity is
1.00 minus the sensible capacity. (If the sensible capacity is
listed at .74 the latent capacity is .26. This means that 74% of
the capacity of the unit is used to remove heat from the air
and 26% is used to remove moisture from the air at standard
test conditions.)
In some applications, information about the sensible/latent
split, or ratio, at conditions other than the standard rating
conditions is needed.
Specifications subject to change.